Monitoring The Plausibility Of Values For The Partial Stroke Test; Fault Correction; Fault Identification - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

10.3.4.15

16 Monitoring the plausibility of values for the partial stroke test

This error message is triggered if, when starting a partial stroke test, the plausibility check of
the "A1.STPOS", "A3.STRKH" and "A4.STRKD" parameters was not successful.
10.4

Fault correction

10.4.1

Fault identification

Diagnostics guide
Fault
In which mode does a fault occur?
Initialization
Manual and automatic modes
In which environment and under which boundary conditions does a fault occur?
Wet environment (e.g. strong rain or constant condensation)
Vibrating (oscillating) control valves
Impact or shock loads (e.g. vapor shocks or breakaway valves)
Moist (wet) compressed air
Dirty (contaminated with solid particles) compressed air
When does a fault occur?
Regularly (reproducible)
Sporadically (not reproducible)
Mostly after a specific operation time
See also
Remedial measures table 2 (Page 233)
Remedial measures table 3 (Page 234)
Corrective measures Table 4 (Page 235)
Remedial measures table 5 (Page 236)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
Alarm, error, and system messages
10.4 Fault correction
Corrective measures, see
table
1
2
3
2
2
5
5
2
2
3
1
2
5
2
3
4
5
3
4
5
231