10.3.4.15
16 Monitoring the plausibility of values for the partial stroke test
This error message is triggered if, when starting a partial stroke test, the plausibility check of
the "A1.STPOS", "A3.STRKH" and "A4.STRKD" parameters was not successful.
10.4
Fault correction
10.4.1
Fault identification
Diagnostics guide
Fault
In which mode does a fault occur?
Initialization
•
Manual and automatic modes
•
In which environment and under which boundary conditions does a fault occur?
Wet environment (e.g. strong rain or constant condensation)
•
Vibrating (oscillating) control valves
•
Impact or shock loads (e.g. vapor shocks or breakaway valves)
•
Moist (wet) compressed air
•
Dirty (contaminated with solid particles) compressed air
•
When does a fault occur?
Regularly (reproducible)
•
Sporadically (not reproducible)
•
Mostly after a specific operation time
•
See also
Remedial measures table 2 (Page 233)
Remedial measures table 3 (Page 234)
Corrective measures Table 4 (Page 235)
Remedial measures table 5 (Page 236)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
Alarm, error, and system messages
10.4 Fault correction
Corrective measures, see
table
1
2
3
2
2
5
5
2
2
3
1
2
5
2
3
4
5
3
4
5
231