Functional safety

8.4 Settings

8.4
Settings
No special parameter settings are required for the safety function.
Protection against configuration changes
You should attach the housing cover so that the device is protected against unwanted and
unauthorized changes/operation.
Checking the safety function
Prerequisite for checking the safety function
● Positioner is in operation.
● The actuator belonging to the positioner is not in the safety position.
Procedure
● On the positioner, switch the signal source to 0 mA or the power supply source to 0 V.
● Reduce the inlet pressure (PZ) to a third of the maximum supply pressure.
● Always carry out the validation of the safety function with positioner and valve under
operating conditions.
Result
The actuator brings the valve to the specified safety position.
See also
Safety function (Page 139)
8.5

Safety characteristics

The safety characteristics necessary for use of the system are listed in the SIL declaration of
conformity. These values apply under the following conditions:
● The positioner is only used in applications with low demand rate for the "Low demand
mode".
● The positioner is blocked against unwanted and unauthorized changes/operation.
● The signal source with 0 mA or the power supply source with 0 V for the SIPART PS2
positioner is generated by a safe system that fulfills SIL 2 for single-channel operation.
● The connected single-acting type actuator returns the valve to the safe end position by
spring force in the following scenarios:
– With a chamber pressure (Y1 connection) up to a third of the maximum available
142
supply air pressure (PZ connection)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB