Xdiag Parameter; Meaning Of Error Codes; Remaining Control Deviation; Device Not In "Automatic" Mode - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Alarm, error, and system messages
10.3 Online diagnostics
10.3.3

XDIAG parameter

You can use the advance diagnostics parameters to display fault messages in one, two or
three stages. In addition to the fault message output, alarm outputs 1 and 2 are then used.
For this purpose, set the "XDIAG" parameter as described in the following table:
Settings of XDIAG
OFF
On 1
On 2
On 3
Possible settings of the "XDIAG" parameter
10.3.4

Meaning of error codes

10.3.4.1

1 Remaining control deviation

The deviation between the setpoint and the actual value is continuously monitored in
"Automatic" mode. The fault message for a remaining control deviation is activated
depending on the setting of the application parameters " TIM" - monitoring time for setting
the fault messages - and " LIM" - response threshold for the fault message. The fault
message is cancelled as soon as the control deviation drops below the response threshold.
This monitoring function is always active.
10.3.4.2

2 Device not in "Automatic" mode

When the device is not in automatic mode, an error message is generated if the ' FCT'
parameter (function of fault message output) is set correctly. A warning is then sent to the
control system if the device was switched to manual or configuration mode on-site.
10.3.4.3

3 Binary input BIN1 or BIN2 active

If the binary input is activated, an error message is generated when the " FCT" parameter
(function of fault message output) and the "BIN1" parameter (function of binary input 1) are
set correctly. For example, it can be a switch to monitor the packing glands, a temperature
switch or a limit switch (e.g. for pressure).
Binary input 2 (in the optional alarm module) can be configured in a similar manner.
228
Message due to
Advanced diagnostics not activated
Fault message output for threshold 3 fault messages (one-stage)
Fault message output for threshold 3 fault messages and alarm output 2 for threshold 2
fault messages (two-stage)
Fault message output for threshold 3 fault messages and alarm output 2 for threshold 2
fault messages and alarm output 1 for threshold 1 fault messages (three-stage)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB