Alarm, error, and system messages
10.2 Diagnostics
10.2.3
Overview of diagnostics values
Explanatory notes on the following table
● The "Representable diagnostics values" column shows the factory settings for the
diagnostics parameters in bold type.
● The "Properties" column shows the properties of the diagnostics parameters:
–
–
–
–
Overview of diagnostics values
No.
Abbreviation
Meaning
1
STRKS
Number of total strokes
2
CHDIR
Number of changes in direction
3
CNT
Number of fault messages
4
A1CNT
Number of alarms 1
5
A2CNT
Number of alarms 2
6
HOURS
Number of operating hours
7
HOURR
Resettable operating hours counter
8
WAY
Determined actuator travel
9
TUP
Travel time UP
10
TDOWN
Travel time DOWN
11
LEAK
Leakage test
12
PST
Monitoring of the partial stroke test
13
PRPST
Time since the last partial stroke test
14
NXPST
Time until the next partial stroke test
15
DEVI
Dynamic control valve behavior
16
ONLK
Pneumatic leakage
17
STIC
Stiction (slipstick)
208
①
Diagnostics value can be read and reset.
②
Diagnostics value can be read but not reset.
③
Diagnostics value can be read but not reset. A function can be executed.
④
Diagnostics value can be read, manually reset, and manually changed.
Representable
Unit
diagnostics val-
ues
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
-
0 ... 4.29E9
Hours
0 ... 4.29E9
0 ... 130
mm or °
0.0 / 0 ... 1000
s
0.0 / 0 ... 1000
s
- / 0.0 ... 100.0
%/minute
OFF / ###.#,
s for ###.#
FdInI, notSt,
SdtSt, fdtSt, no-
toL, Strt, StoP
###, notSt, Sdtst,
Days
fdtSt
OFF / ###
Days
OFF / 0.0 ...
%
100.0
OFF / 0.0 ...
-
100.0
OFF / 0.0 ...
%
100.0
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
Properties
①
①
①
①
①
②
①
②
②
②
③
③
②
②
②
②
②