Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of the DI 16X24VDC HA
You have the following setting options:
Table 4-1
Parameters and their defaults
Parameter
Diagnostics,
Missing supply voltage L+
IO redundancy
Diagnostics
Short-circuit to ground
Diagnostics,
Wire break
1
Check for wire break
Channel activated
Input delay
2
Pulse stretching
2
Hardware interrupts rising
edge
2
16
Value range
● Enabled
● Disabled
● None
● 2 modules
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● None
● 0.05 ms
● 0.1 ms
● 0.4 ms
● 0.8 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms
● None
● 0.05 s
● 0.1 s
● 0.2 s
● 0.5 s
● 1 s
● 2 s
● Enabled
● Disabled
Default
Parameter re‐
assignment in
RUN
Enabled
Yes
None
No
Enabled
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
3.2 ms
Yes
None
Yes
Disabled
Yes