Siemens SIMATIC ET 200SP Manual page 27

Ha digital input module di 16x24vdc
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Article number
Input delay (for rated value of input voltage)
for standard inputs
Cable length
● shielded, max.
● unshielded, max.
Encoder
Connectable encoders
● 2-wire sensor
Interrupts/diagnostics/status information
Diagnostics function
Alarms
● Diagnostic alarm
● Hardware interrupt
Diagnostic messages
● Diagnostic information readable
● Monitoring the supply voltage
● Monitoring of encoder power supply
● Wire-break
● Short-circuit to M
Diagnostics indication LED
● MAINT LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display
● for channel diagnostics
● for module diagnostics
Potential separation
Potential separation channels
● between the channels
● between the channels and backplane bus
● between the channels and the power supply
Isolation
Isolation tested with
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
Digital Input Module DI 16x24VDC HA (6DL1131-6BH00-0PH1)
Manual, 05/2017, A5E39265608-AA
parameterizable
permissible quiescent current (2-wire
sensor), max.
parameterizable
of the electronics
Technical specifications
6DL1131-6BH00-0PH1
Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 /
20 ms
1 000 m
600 m
Yes
1.5 mA
Yes
Yes; channel by channel
Yes; channel by channel
Yes
Yes; Module-wise
Yes
Yes
Yes; Channel-by-channel, optional protective cir‐
cuit for preventing wire-break diagnostics in the
case of simple encoder contacts: 15 kOhm to 18
kOhm
Yes; Encoder supply to M, channel by channel
Yes; yellow LED
Yes; Green LED
Yes; Red LED
Yes; Green/red LED
No
Yes
No
1 500 V DC/1 min, type test
-40 °C