Parameter
Hardware interrupts falling
edge
2
Potential group
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled. If you use a simple
1
encoder contact, you need to connect a parallel resistor to enable wire break diagnostics in the open state (sensor resistance
for wire break diagnostics: 15 kΩ to 18 kΩ).
The input delay is switched off on all channels when high precision time stamping is activated. When high precision time
2
stamping is activated, pulse stretching and the rising/falling edge hardware interrupt are deactivated on all channels (not
adjustable).
Parameter reassignment
Each configuration change resets the corresponding reaction. Changing the configuration of
a function does not affect other functions.
Digital Input Module DI 16x24VDC HA (6DL1131-6BH00-0PH1)
Manual, 05/2017, A5E39265608-AA
Value range
● Enabled
● Disabled
● Use potential group of the left
module
● Allow new potential group
4.2 Module/channel parameters
Default
Parameter re‐
assignment in
RUN
Disabled
Yes
Use potential
No
group of the left
module
Parameters
Efficiency range
Channel
Module
17