Module/Channel Parameters - Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manual

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA:
Table of Contents

Advertisement

Parameters

5.2 Module/channel parameters

5.2
Module/channel parameters
Parameters of the DQ 32x24VDC/0.5A HA
You have the following setting options:
Table 5-1
Parameters and their default settings
Parameter
Diagnostics,
Missing supply voltage L+
Diagnostics
Short-circuit to ground
Channel activated
Reaction to CPU STOP
Substitute value
1
Potential group
Double-wide terminal block
2
Only applicable when the value "Output substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
1
I/O module on terminal block with potential distributor: Select the "Double-width terminal block" parameter in the hardware
2
properties for the I/O module.
18
Value range
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Shutdown
● Keep last value
● Output substitute value
● 0
● 1
● Use potential group of the left
module
● Allow new potential group
● Enabled
● Disabled
Default
Enabled
Enabled
Enabled
Shutdown
0
Use potential
group of the left
module
Disabled
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
Parameter re‐
Efficiency range
assignment in
RUN
Yes
Module
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
No
Module
No
Configuration
(HW Config)
Manual, 09/2018, A5E39265993-AA