Diagnostics Messages And Maintenance Events - Siemens SIMATIC ET 200SP Manual

Ha digital input module di 16x24vdc
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
A.4

Diagnostics messages and maintenance events

Diagnostics messages
A diagnostics message is generated for each diagnostics event and the DIAG LED on the
DI 16×24VDC HA flashes red or the MT LED lights up yellow.
In addition, channel-specific channel diagnostics are displayed through the corresponding
channel error/status LEDs.
The diagnostics messages can be read in the diagnostics buffer of the CPU, for example.
Diagnostic messages are assigned either channel-specific to an input or assigned as module
messages to all inputs. All channels are switched off for diagnostics messages that affect the
entire module. Only the corresponding digital input is affected by diagnostics messages, which
refer to individual channels.
Table A-1
Diagnostic messages, their meanings and remedy options
Diagnostics mes‐
Error
sage
code
Wire break
6
H
Parameter assign‐
10
H
ment error
Supply voltage
11
H
missing
Hardware interrupt
16
H
lost
Channel/compo‐
1F
H
nent temporarily
unavailable
Short-circuit/over‐
10E
load at external en‐
coder supply
Shutdown on but‐
122
ton activation
38
Assignment
Channel
Impedance of encoder circuitry is too high Use another type of encoder
Wire break between the module and sen‐
sor
Channel not connected (open)
Module
● Parameter assignment does not match
● Incorrect parameter assignment
Module
Missing or insufficient supply voltage L+
Module
Error is reported because the events occur
faster than they can be processed in the
system.
Module
Firmware update is in progress or has
been canceled during the update.
The module does not read any process
values in this state.
Channel
Short-circuit of the encoder supply to
H
ground
Module
The output disable switch was activated
H
Meaning
the terminal block used
Digital Input Module DI 16x24VDC HA (6DL1131-6BH00-0PH1)
Remedy
or wiring, for example, use
conductors with a larger cross-
section
Connect the cable
● Disable diagnostics
● Connect encoder contact
with a 15 kΩ to 18 kΩ
resistor.
● Switch off wire break check
● Correct the parameter
assignment
● Check terminal block
● Check the supply voltage L
+ on the terminal block
● Check terminal block
● Restart the firmware
update
● Wait for firmware update
Correction of the process wir‐
ing
Pull module
Manual, 05/2017, A5E39265608-AA