Recognition Time - Sensaphone 1108 User Manual

Sensaphone telephone
Hide thumbs Also See for 1108:
Table of Contents

Advertisement

Sensaphone
®
Model 1108 User's Manual
5.10.3 Programming High Sound Alarm Recognition Time
The Recognition Time for sound alarm monitoring ranges from 2
seconds to 59 seconds. The default value is 8 seconds.
1.
Press SET.
2.
Press RECOGNITION TIME.
3.
Press SOUND. The Model 1108 responds: "Enter seconds. "
4.
Using the number keys, enter the number of seconds. The
Model 1108 will recite the digits as they are pressed.
5.
Press ENTER.
82