2. Press RECOGNITION TIME.
3. Press the corresponding input key (1 to 8).
The Model 1108 recites the programmed Recognition Time for
that input.
5.4
Establishing High and Low Temperature Limits
High and low temperature limits can be separately programmed
for each input configured as temperature. Limits can range from
-20° to +150° Fahrenheit, or from -30° to 65° Celsius.
When temperature limits exceed high or low settings, the Model
1108 will dial out with an alarm message. Default settings are:
10° F for low temperature and 100° F for high temperature.
5.4.1 Programming Temperature Limits for a Selected Input
1. Press SET.
2. Press TEMP LIMITS.
3. From the number keys, press a number (from 1 to 8) that
corresponds to the temperature input being programmed.