2. Press CALIBRATE.
3. Press the number (1 to 8) of the selected temperature input to
be calibrated.
4. Enter the number required to offset the current temperature
reading so a correct reading is obtained.
• To program a positive offset number (up to +10 degrees),
enter the number on the keypad. The Model 1108 recites the
digits as they are pressed.
• To program a negative offset number (up to -10 degrees),
first press PAUSE. The unit responds with a "beep. " Next,
enter the number on the keypad. The unit recites the digits as
they are pressed.
5. Press ENTER. The Model 1108 responds:"Enter. "
If you find that your calibration offset exceeds more
than + 5 or -5 degrees, other complicating factors
could be affecting normal operation of the Model
1108. Call Sensaphone, Inc. for technical assistance.