The Model 1104 audibly recites the current status of every input.
In a Status Report, each input is first identified by its input
number, followed by a report that specifies parameters currently
affecting that input. If an input is disabled, the word "Off"
immediately follows the number recited for that input.
For example, input 3 is configured as a normally open, dry
contact input. During the Status Report:
• If disabled, the Model 1104 recites:
"Number 3—Off—OK, " for input 3.
• If enabled, the Model 1104 recites:
"Number 3—OK, " for input 3.
In another example, input 2 is configured as a temperature input.
The current temperature is 76 degrees. During a Status Report:
• If disabled, the Model 1104 recites:
"Number 2—Off—76 degrees—OK. "
• If enabled, the Model 1104 recites:
"Number 2—76 degrees—OK. "

5.3 Input Recognition Time

The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial- out
is activated. This time period is programmable, from 0 minutes, 0
seconds (for immediate response) up to a period of 272 minutes, 0
seconds. If an alert condition begins and then clears within the
established Recognition Time, no dial-out will occur. When an
alert condition continues beyond the programmed Recognition
Time, the Model 1104 initiates dial-out. The default setting for
Input Recognition Time is 0 minutes, 3 seconds.

5.3.1 Programming Input Recognition Time

1. Press SET.
SET
#
2. Press RECOGNITION TIME.
7
RECOGNITION
TIME
3. Press the number (1 to 4) of the selected input to be
66