SMA Solar Technology AG
11 Technical Data
11.1 DC/AC
11.1.1 Sunny Tripower 5000TL / 6000TL / 7000TL
DC Input
Maximum DC power at
cos φ = 1
Maximum input voltage
MPP voltage range
Rated input voltage
Minimum usable input voltage
Initial input voltage
Maximum input current, input A
Maximum input current, input B
Maximum input current per
string, input A
Maximum input current per
string, input B
Maximum short-circuit current,
input A*
Maximum short-circuit current,
input B*
Maximum reverse current from
the inverter in the system for
max. 1 ms
Number of independent MPP in-
puts
Strings per MPP input
Overvoltage category in accor-
dance with IEC 60664-1
* In accordance with IEC 62109-2: ISC PV
Operating Manual
STP 5000TL-20
5100 W
1000 V
245 V to 800 V
580 V
150 V
188 V
11 A
10 A
11 A
10 A
17 A
15 A
0 A
2
2
II
STP 6000TL-20
6125 W
1000 V
295 V to 800 V
580 V
150 V
188 V
11 A
10 A
11 A
10 A
17 A
15 A
0 A
2
2
II
STP5-12TL-20-BE-en-15
11 Technical Data
STP 7000TL-20
7175 W
1000 V
290 V to 800 V
580 V
150 V
188 V
15 A
10 A
15 A
10 A
25 A
15 A
0 A
2
2
II
59