Connecting The Multifunction Relay; Procedure For Connecting The Multifunction Relay; Operating Modes Of The Multifunction Relay; Connection Options - SMA 5000TL Operating Manual

Sunny tripower
Hide thumbs Also See for 5000TL:
Table of Contents

Advertisement

6 Electrical Connection
6.4

Connecting the Multifunction Relay

6.4.1

Procedure for connecting the multifunction relay

Procedure
1.
Select for which operating mode you would like to use the
multifunction relay.
2.
Connect to the multifunction relay according to the operat-
ing mode and the associated connection variant.
3.
After commissioning the inverter, change the operating
mode of the multifunction relay, if necessary.
6.4.2

Operating Modes of the Multifunction Relay

Operating mode of multi-
function relay (Mlt.Op-
Mode)
Fault indication (FltInd)
Self-consumption (SelfC-
smp)
Control via communica-
tion (ComCtl)
Battery bank (BatCha)
Fan control (FanCtl)
Switching status grid re-
lay (GriSwCpy)
6.4.3

Connection Options

The connection procedures vary, depending on the operating mode.
Operating mode
Fault indication (FltInd)
Self-consumption (SelfC-
smp)
32
STP5-12TL-20-BE-en-15
Description
The multifunction relay controls a display device (e.g. a warning
light) which, depending on the type of connection, signals either an
error or the undisturbed operation of the inverter.
The multifunction relay switches loads on or off, depending on the
power production of the PV system.
The multifunction relay switches loads on or off according to com-
mands transmitted by a communication product.
The multifunction relay controls the charging of the batteries depend-
ing on the power production of the PV system.
The multifunction relay controls an external fan, depending on the
temperature of the inverter.
The local grid operator may require that a signal is transmitted as
soon as the inverter connects to the utility grid. The multifunction re-
lay can be used to trigger this signal.
Connection option
Using the Multifunction Relay as a Fault Indicator Contact
Controlling loads via the multifunction relay or charging batteries de-
pending on the power production of the PV system
SMA Solar Technology AG
See
Section 6.4.2, page 32
Section 6.4.3, page 32
and Section 6.4.4,
page 37
User manual under
www.SMA-Solar.com