SUNNY MINI CENTRAL 9000TL / 10000TL / 11000TL

with Reactive Power Control

Installation Manual
SMC9-11TLRP-IA-en-51 | IMEN-SMCTLRP | Version 5.1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 9000TL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SMA 9000TL

  • Page 1: With Reactive Power Control

    Front cover PV Inverter SUNNY MINI CENTRAL 9000TL / 10000TL / 11000TL with Reactive Power Control Installation Manual SMC9-11TLRP-IA-en-51 | IMEN-SMCTLRP | Version 5.1...
  • Page 3: Table Of Contents

    Sunny Mini Central ..............15 Type Label ................. 17 Display and LEDs ..............19 Electronic Solar Switch (ESS) ........... 20 SMA Power Balancer ............... 21 Communication ................. 23 Grid Management..............23 Fuse Holders for String Fuses ........... 23 Varistors ..................24 4.10 SMA Grid Guard..............
  • Page 4 Connecting the SMA Power Balancer........43 Installing the String Fuses ............45 Configuration ................47 Checking the Function of the SMA Power Balancer and Setting the Operating Mode............ 47 Changing the Country Data Set ..........48 Setting the Country Data Set for Operation with External Decoupling Protection ..............
  • Page 5 11.3 Disposing of the Inverter............81 12 Technical Data................82 12.1 DC/AC ..................82 12.1.1 Sunny Mini Central 9000TL with Reactive Power Control ...82 12.1.2 Sunny Mini Central 10000TL with Reactive Power Control ..84 12.1.3 Sunny Mini Central 11000TL with Reactive Power Control ..86 12.2 General Data ................
  • Page 6 Table of Contents SMA Solar Technology AG SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 7: Information On This Document

    This document is intended for skilled persons. Only qualified personnel are allowed to perform the tasks described in this manual (see section 2.2 "Qualifications of Skilled Persons", page 11). STSatz_Hinw_Weiterführende Informationen Additional Information Links to additional information can be found at www.SMA-Solar.com: Document title Document type Three-Phase Grid Connection...
  • Page 8 1 Information on this Document SMA Solar Technology AG Symbols Symbol Explanation Indicates a hazardous situation which, if not avoided, will result in death or serious injury Indicates a hazardous situation which, if not avoided, could result in death or serious injury...
  • Page 9 SMA Solar Technology AG 1 Information on this Document Abbreviations Abbreviation Designation Explanation Alternating Current ‒ Direct Current ‒ Digital Signal Processor ‒ European Community ‒ EEPROM Electrically Eraseable ‒ Programmable Read-Only Memory Light-Emitting Diode ‒ Maximum Power Point ‒...
  • Page 10: Safety

    The product may only be used in countries for which it is approved or released by National approval and release SMA Solar Technology AG and the network operator. For safety reasons, it is forbidden to modify the product or install components that are not explicitly STSatz_Best Verwend_Produkt ändern...
  • Page 11: Qualifications Of Skilled Persons

    SMA Solar Technology AG 2 Safety Only use the Sunny Mini Central in accordance with the information provided in the enclosed documentation. Any other application may cause injury to persons or lead to property damage. Mounting the Product • Do not mount the product on flammable construction materials.
  • Page 12: Safety Precautions

    2 Safety SMA Solar Technology AG Safety Precautions Electric Shock High voltages are present in the live components of the inverter. Touching these components can SiHiw_Stromschlag durch hohe Spannungen cause fatal electric shock. • Always disconnect the inverter from voltage sources before performing any work on it as described in this document (see section 9).
  • Page 13: Scope Of Delivery

    SMA Solar Technology AG 3 Scope of Delivery 3 Scope of Delivery Check the scope of delivery for completeness and any externally visible damage. Contact your STSatz_Lieferumfang_Inhalt prüfen specialist dealer if the delivery is incomplete or damaged. Figure 2: Components of the delivery...
  • Page 14 3 Scope of Delivery SMA Solar Technology AG Position Quantity Designation Installation manual, user manual, document set with explanations and certificates, supplementary sheet with the default settings * 1 spare part for the enclosure lid included ** Optional SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 15: Product Description

    SMA Solar Technology AG 4 Product Description 4 Product Description Sunny Mini Central The Sunny Mini Central is a transformerless PV inverter, which converts the direct current of the Aufgabe_SMC-TL PV array to grid-compliant alternating current and feeds it into the electricity grid.
  • Page 16: Symbols On The Inverter

    Prior to performing any work on the inverter, disconnect it from all voltage sources, as described in this document (see section 9). ® ® QR Code The QR Code links to the SMA Bonus Programme (for information see www.SMA-Bonus.com). SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 17: Type Label

    Field for additional information, e.g. details of standards Inverter manufacture date (year-month-day) You require the information on the type label to use the product safely and for questions to the STSatz_Typenschild_Funktionsbeschreibung SMA Service Line. The type label must be permanently attached to the product. Installation Manual SMC9-11TLRP-IA-en-51...
  • Page 18: Symbols On The Type Label

    4 Product Description SMA Solar Technology AG Symbols on the Type Label SMCTLRP_Tabelle Symbole auf Typenschild Icon Designation Explanation Danger to life due to high The inverter operates at high voltages. voltages All work on the inverter must be carried out by skilled persons only.
  • Page 19: Display And Leds

    SMA Solar Technology AG 4 Product Description Icon Designation Explanation Korean mark of conformity The inverter complies with the requirements of the applicable Korean guidelines. Chinese mark of conformity The inverter complies with the requirements of the applicable Chinese guidelines.
  • Page 20: Electronic Solar Switch (Ess)

    4 Product Description SMA Solar Technology AG Electronic Solar Switch (ESS) The ESS and the DC connectors form a DC load disconnect unit. Aufgabe_ESS There are two types of ESS with different plug designs. The function of the ESS is identical in both cases.
  • Page 21: Sma Power Balancer

    The SMA Power Balancer is a function of the Sunny Mini Central, which allows three-phase grid connection. Design of a three - phase feed-in unit with three Sunny Mini Central inverters with SMA Power Balancer Figure 7: Using the SMA Power Balancer, you can connect three Sunny Mini Central inverters to a three-phase feed-in unit, preventing unbalanced loads.
  • Page 22: Operating Mode

    SMA Solar Technology AG Operating mode Explanation The SMA Power Balancer is deactivated (default setting). If one of the three inverters indicates a line voltage error or a device fault, only the inverter affected disconnects from the electricity grid. The other two inverters continue to feed in at full power.
  • Page 23: Communication

    PV modules used and the number of strings directly connected to the inverter (for information on the string fuses, see the Technical Information "Use of String Fuses" at www.SMA-Solar.com). Use only the string fuses available from SMA Solar Technology AG (see section 13 "Accessories", page 91).
  • Page 24: Varistors

    SMA Grid Guard code, after ten feed-in hours (for information on changing parameters, see the manual for the communication product). You will receive the SMA Grid Guard code from SMA Solar Technology AG (to apply for the SMA Grid Guard code, see the certificate "Application for SMA Grid Guard Code"...
  • Page 25: Mounting

    SMA Solar Technology AG 5 Mounting 5 Mounting Selecting the Mounting Location Requirements for the mounting location: WaHiw_Lebensgefahr durch Feuer und Explosion Danger to life due to fire or explosion Despite careful construction, electrical devices can cause fires. • Do not mount the inverter on flammable construction materials.
  • Page 26 5 Mounting SMA Solar Technology AG Dimensions for wall mounting: Figure 8: Dimensions of the wall mounting bracket and dimensions of the holes for the optional anti-theft device in the inverter enclosure SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 27 SMA Solar Technology AG 5 Mounting Observe recommended clearances: Figure 9: Recommended clearances • Observe the recommended clearances to the walls as well as to other inverters or objects. This ensures adequate heat dissipation and sufficient space to remove the ESS.
  • Page 28: Mounting The Inverter

    5 Mounting SMA Solar Technology AG Mounting the Inverter Additionally required mounting material (not included in the scope of delivery): ☐ At least two screws which are suitable for the weight of the inverter and the surface ☐ At least two washers that are suitable for the screws ☐...
  • Page 29 SMA Solar Technology AG 5 Mounting 5. If the inverter is to be secured against theft, mark the drill hole for the attachment of the safety screw: • Hook the inverter into the wall mounting bracket. • Mark the drill hole on the left-hand side or right-hand side.
  • Page 30 5 Mounting SMA Solar Technology AG 7. Attach the inverter to the wall mounting bracket on both sides using the M6x8 screws provided and an Allen key (AF 5). Only tighten the screws hand-tight. That prevents the inverter being lifted out.
  • Page 31: Electrical Connection

    SMA Solar Technology AG 6 Electrical Connection 6 Electrical Connection Safety during Electrical Connection Electric Shock When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC SiHiw_Stromschlag durch hohe Spannung conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks.
  • Page 32: Overview Of The Connection Area

    For connecting the ESS Negative DC connector with filler plug For connecting the negative DC cables Enclosure opening For routing the data cables through Socket For connecting the SMA Power Balancer Enclosure opening For routing the AC cable through SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 33: Interior View

    SMA Solar Technology AG 6 Electrical Connection 6.2.2 Interior View Figure 12: Components and connection areas in the interior of the inverter Item Designation Explanation Jumper slot For checking the fans Terminal For the AC cable Flat male tabs For earthing the cable shield of the...
  • Page 34: Ac Connection

    ☐ When designing the conductor cross-section, all factors must be taken into consideration (see the design program "Sunny Design" from software version 2.0 at www.SMA-Solar.com). ☐ The maximum cable length subject to conductor cross-section must be observed. Useful hint: If you group three inverters to a three-phase plant with symmetrical feed-in, the line losses are halved.
  • Page 35: Connecting The Inverter To The Electricity Grid

    • If an external residual-current device is required, install a residual-current device which trips at a residual current of 100 mA or higher (for details on selecting a residual-current device, see the Technical Information "Criteria for Selecting a Residual-Current Device" at www.SMA-Solar.com). SMC Classic_Überspannungskategorie Overvoltage category The inverter can be used in grids of installation category III or lower in accordance with IEC 60664-1.
  • Page 36 6 Electrical Connection SMA Solar Technology AG 9. Connect the AC cable to the terminal block for the AC cable using a screwdriver: • Connect PE to terminal PE. • Connect N to terminal N. • Connect L to terminal L.
  • Page 37: Additional Earthing Of The Enclosure

    SMA Solar Technology AG 6 Electrical Connection 6.3.3 Additional Earthing of the Enclosure You can additionally earth the inverter enclosure if a second earthing or equipotential bonding is required locally. This prevents touch current if the original protective conductor fails.
  • Page 38: Dc Connection

    6 Electrical Connection SMA Solar Technology AG DC Connection 6.4.1 Conditions for DC Connection Requirements for the PV modules: Funkt.Titel_Anforderungen an die PV-Module ☐ All PV modules must be of the same type. ☐ The same number of series-connected PV modules must be connected to all strings.
  • Page 39: Cable Requirements

    SMA Solar Technology AG 6 Electrical Connection Cable requirements: The cable must be of type PV1-F, UL-ZKLA or USE2 and comply with the following properties: ☐ External diameter: 5 mm … 8 mm. ☐ Conductor cross-section: 2.5 mm² … 6 mm²...
  • Page 40 6 Electrical Connection SMA Solar Technology AG ✖ Is the stranded wire not visible in the chamber? The cable is not correctly in place. • Release the clamping bracket. To do so, insert a screwdriver (blade width: 3.5 mm) into the clamping bracket and lever it open.
  • Page 41: Connecting The Pv Array

    SMA Solar Technology AG 6 Electrical Connection 6.4.3 Connecting the PV Array WaHiw_Leerlaufspannung darf max. Eingangsspannung nicht überschreiten Destruction of the inverter due to overvoltage If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the inverter, the inverter can be destroyed by the overvoltage.
  • Page 42 6 Electrical Connection SMA Solar Technology AG Damage to the inverter due to moisture penetration The inverter is only properly sealed when all the unused DC inputs are closed with DC connectors and sealing plugs. • DO NOT insert the sealing plugs DIRECTLY into the DC inputs on the inverter.
  • Page 43: Connecting The Sma Power Balancer

    Connecting the SMA Power Balancer You need a special Y cable to connect the SMA Power Balancer. The Y cable is not a standard accessory. You can order the Y cable from SMA Solar Technology AG (see section 13 "Accessories", page 91).
  • Page 44 ☐ All three inverters must be equipped with the SMA Power Balancer plug-in system. Hint: If an inverter is not equipped with a SMA Power Balancer plug-in system, you can order a retrofit kit (see section 13 "Accessories", page 91).
  • Page 45: Installing The String Fuses

    6. Commission the inverter (see section 8 "Commissioning", page 51). 7. To use the SMA Power Balancer function, activate the SMA Power Balancer via a communication product (see section 7.1 "Checking the Function of the SMA Power Balancer and Setting the Operating Mode", page 47).
  • Page 46 6 Electrical Connection SMA Solar Technology AG 3. Insert the string fuse into the fuse extractor. 4. Insert the fuse extractor with the string fuse into the fuse holder. 5. Commission the inverter (see section 8 "Commissioning", page 51). SMC9-11TLRP-IA-en-51...
  • Page 47: Configuration

    The connection of the SMA Power Balancer is probably faulty or the parameter Power Balancer is not set to PhaseGuard. • Check the connection and setting of the SMA Power Balancer. If the connection is correct and the parameter PowerBalancer is set to PhaseGuard, contact the SMA Service Line.
  • Page 48: Changing The Country Data Set

    ☐ The responsible network operator must approve changes of grid-relevant parameters. ☐ The SMA Grid Guard code for changing the grid-relevant parameters must be available (to apply for an "SMA Grid Guard" code, see the certificate "Application for SMA Grid Guard Code" at www.SMA-Solar.com).
  • Page 49: Setting The Country Data Set For Operation With External Decoupling Protection

    ☐ The responsible network operator must approve changes of grid-relevant parameters. ☐ The SMA Grid Guard code for changing the grid-relevant parameters must be available (to apply for an "SMA Grid Guard" code, see the certificate "Application for SMA Grid Guard Code" at www.SMA-Solar.com).
  • Page 50: Changing The Display Language

    7 Configuration SMA Solar Technology AG Changing the Display Language You can change the display language of the inverter. Various languages are available depending on the country data set selected. Figure 14: Two switches at the bottom of the display assembly 1.
  • Page 51: Commissioning

    ☑ The green LED is glowing and the start-up phase begins. The display shows the device type, firmware version, country data set and operating mode of the SMA Power Balancer consecutively. After the start-up phase has been completed, the current power, reactive power and displacement power factor cos φ...
  • Page 52 ☑ The green LED is glowing and the start-up phase begins. The display shows the device type, firmware version, country data set and operating mode of the SMA Power Balancer consecutively. After the start-up phase has been completed, the current power, reactive power and displacement power factor cos φ...
  • Page 53: Disconnecting The Inverter

    SMA Solar Technology AG 9 Disconnecting the Inverter 9 Disconnecting the Inverter Before performing any work on the inverter, always disconnect it as described in this section. 1. Disconnect the miniature circuit-breaker and secure against reconnection. 2. Remove the ESS.
  • Page 54 9 Disconnecting the Inverter SMA Solar Technology AG 6. Ensure that no voltage is present at the DC inputs of the inverter using a suitable measuring device. 7. Unscrew all screws of the enclosure lid and remove the enclosure lid.
  • Page 55 SMA Solar Technology AG 9 Disconnecting the Inverter Damage to the inverter due to electrostatic discharge The internal components of the inverter can be irreparably damaged by electrostatic discharge. • Earth yourself before touching any components. Installation Manual SMC9-11TLRP-IA-en-51...
  • Page 56: Troubleshooting

    10 Troubleshooting SMA Solar Technology AG 10 Troubleshooting 10.1 LED Signals The LEDs indicate the operating state of the inverter. Designation Status Explanation Green LED Glowing Operation The specific status message is shown in the display (see section 10.2.2 "Status Messages", page 59).
  • Page 57 SMA Solar Technology AG 10 Troubleshooting Damage to the inverter due to moisture and dust intrusion If the ESS is not plugged in or incorrectly plugged in during operation, moisture and dust can penetrate the inverter. If the ESS is not correctly plugged in, this can cause contacts in the ESS to wear or the ESS might fall out of the socket.
  • Page 58: Display Messages

    10 Troubleshooting SMA Solar Technology AG 10.2 Display Messages 10.2.1 Measurement Channels Measurement channels are measured values which are shown on the display. The measurement channels can also be read out using a communication product. Measurement channel Explanation Balancer Indicates the operating mode of the inverter which is set under the operating parameter PowerBalancer.
  • Page 59: Status Messages

    4.6 kVA. The inverter is part of a three-phase system with two further inverters and is equipped with the SMA Power Balancer to prevent the formation of unbalanced loads. Derating This message can have several causes: •...
  • Page 60: Errors, Faults, Warnings

    "ACVtgRPro" parameter. If the mains voltage is permanently in the permissible range and this message is still displayed, contact the SMA Service Line. SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 61 • Ensure that the AC cable is correctly connected (see section 6.3.2 "Connecting the Inverter to the Electricity Grid", page 35). • If the AC cable is connected correctly and this message is still displayed, contact the SMA Service Line. Check Varistor At least one of the varistors is defective.
  • Page 62 • Ensure that the mains frequency is in the permissible range. If the mains frequency is in the permissible range and this message is still displayed, contact the SMA Service Line. HW-Signal Internal measurement fault or the hardware is defective.
  • Page 63 The parameter „PowerBalancer“ is set to the operating modes „PhaseGuard“ or „FaultGuard“ (description of the operating modes of the SMA Power Balancer, see Section section 4.5). REL_INV_CLOSE One of the grid relays does not close. The inverter checks the relays...
  • Page 64 Corrective measures: • If this message is displayed frequently, contact the SMA Service Line. Shutdown Temporary inverter fault Corrective measures: • Contact the SMA Service Line. SMC9-11TLRP-IA-en-51 Installation Manual...
  • Page 65 • If the DC voltage is below the maximum input voltage of the inverter, connect the DC connectors to the inverter again. • If this message is repeated frequently, disconnect the inverter (see section 9) and contact the SMA Service Line. Installation Manual SMC9-11TLRP-IA-en-51...
  • Page 66: Cleaning The Fans

    10 Troubleshooting SMA Solar Technology AG Message Cause and corrective measures UZWK-Max The internal hardware monitoring system has detected an overvoltage in the intermediate circuit of the inverter. UzwkMax Corrective measures: • If this message is displayed frequently, contact the SMA Service Line.
  • Page 67 SMA Solar Technology AG 10 Troubleshooting 4. Check whether the fan is soiled. If the fan is soiled, remove the fan: • Use a screwdriver to push the two detents at the right-hand edge of the fan guard to the right-hand side and remove them from the retainer.
  • Page 68: Checking The Fans

    Check the fan installation. If the fans were installed correctly, contact the SMA Service Line. 5. Select the parameter Fan-Test and set it to 0 or Fan test and set it to Off.
  • Page 69 If there is no air coming out of the ventilation grids or the fans are making unusual noises, then presumably the fans were not installed properly. Check the fan installation. If the fans were installed correctly, contact the SMA Service Line. 5. Disconnect the inverter from all voltage sources (see section 9).
  • Page 70: Cleaning The Ventilation Grids

    10 Troubleshooting SMA Solar Technology AG 10.5 Cleaning the Ventilation Grids 1. Remove the ventilation grids towards the side. Damage to the inverter due to foreign bodies • Do not remove the ventilation grids permanently, otherwise foreign bodies could enter into the enclosure.
  • Page 71: Checking The Ess For Wear

    SMA Solar Technology AG 10 Troubleshooting 10.6 Checking the ESS for Wear Depending on the design of the ESS, you can recognise wear either on the metal mounting tabs or on the plastic of the ESS. 1. Remove the ESS.
  • Page 72: Checking The Pv Plant For Earth Faults

    10 Troubleshooting SMA Solar Technology AG Damage to the inverter due to moisture and dust intrusion If the ESS is not plugged in or incorrectly plugged in during operation, moisture and dust can penetrate the inverter. If the ESS is not correctly plugged in, this can cause contacts in the ESS to wear or the ESS might fall out of the socket.
  • Page 73 • Determine the location of the earth fault via the ratio of the two measured voltages. • Eliminate the earth fault. If there is no earth fault and the message is still displayed, contact the SMA Service Line. Example: Location of the earth fault The example shows an earth fault between the second and third PV module.
  • Page 74: Checking The Function Of The Varistors

    10 Troubleshooting SMA Solar Technology AG 10.8 Checking the Function of the Varistors If the red LED is flashing and the inverter displays the message Check Varistor, one of the varistors may be defective. Check the function of each varistor as described in the following.
  • Page 75 If there is no conductive connection, the varistor is defective. SMA Solar Technology AG recommends replacing all varistors immediately. • Order new varistors and insertion tools (see section 13 "Accessories", page 91).
  • Page 76: Replacing The Varistors

    10 Troubleshooting SMA Solar Technology AG 10.9 Replacing the Varistors Proceed as follows to replace each varistor. 1. Disconnect the inverter from all voltage sources (see section 9). 2. Insert the insertion tool into the clamp contacts of the connecting terminal plate.
  • Page 77: Checking The Function Of The String Fuses

    SMA Solar Technology AG 10 Troubleshooting 10.10 Checking the Function of the String Fuses If the red LED is flashing and the inverter displays the message DC fuse, at least one of the string fuses may have tripped or be defective. Each string fuse is assigned to one string.
  • Page 78 10 Troubleshooting SMA Solar Technology AG 4. Use a continuity tester to measure whether the string fuse is conductive. If the string fuse is not conductive, the string fuse is defective. Replace all string fuses immediately. • Order a new string fuse (see section 13 "Accessories", page 91).
  • Page 79: Replacing The String Fuses

    It cannot be guaranteed that commercially available string fuses will function correctly. In the event of an error, the string fuses can burn off. • Install only string fuses available from SMA Solar Technology AG in the inverter. Proceed as follows to replace each string fuse: 1.
  • Page 80: Decommissioning

    2. Remove the AC cable from the inverter. 3. If a data cable is connected, remove the data cable from the inverter. 4. If the SMA Power Balancer is connected, remove the cable of the SMA Power Balancer. 5. Close the inverter: •...
  • Page 81: Packing The Inverter

    • Dispose of the inverter in accordance with the locally applicable disposal regulations for electronic waste. Return the inverter at your own cost to SMA Solar Technology AG (see section 14 "Contact", page 92). Label the package "ZUR ENTSORGUNG" ("FOR DISPOSAL").
  • Page 82: Technical Data

    12 Technical Data SMA Solar Technology AG 12 Technical Data 12.1 DC/AC 12.1.1 Sunny Mini Central 9000TL with Reactive Power Control DC Input Maximum DC power at cos φ = 1 9,300 W 700 V Maximum input voltage MPP voltage range 333 V …...
  • Page 83 SMA Solar Technology AG 12 Technical Data AC Output Rated power at 230 V, 50 Hz 9,000 W Maximum apparent AC power 9,000 VA Rated grid voltage 230 V Nominal AC voltage 220 V / 230 V / 240 V AC voltage range 180 V …...
  • Page 84: Sunny Mini Central 10000Tl With Reactive Power Control

    12 Technical Data SMA Solar Technology AG 12.1.2 Sunny Mini Central 10000TL with Reactive Power Control DC Input Maximum DC power at cos φ = 1 10,350 W 700 V Maximum input voltage MPP voltage range 333 V … 500 V...
  • Page 85 SMA Solar Technology AG 12 Technical Data AC Output Rated power at 230 V, 50 Hz 10,000 W Maximum apparent AC power 10,000 VA Rated grid voltage 230 V AC nominal voltage 220 V / 230 V / 240 V AC voltage range 180 V …...
  • Page 86: Sunny Mini Central 11000Tl With Reactive Power Control

    12 Technical Data SMA Solar Technology AG 12.1.3 Sunny Mini Central 11000TL with Reactive Power Control DC Input Maximum DC power at cos φ = 1 11,400 W 700 V Maximum input voltage MPP voltage range 333 V … 500 V...
  • Page 87 SMA Solar Technology AG 12 Technical Data AC Output Rated power at 230 V, 50 Hz 11,000 W Maximum apparent AC power 11,000 VA Rated grid voltage 230 V AC nominal voltage 220 V / 230 V / 240 V AC voltage range 180 V …...
  • Page 88: General Data

    12 Technical Data SMA Solar Technology AG 12.2 General Data Width ⨯ height ⨯ depth with 468 mm ⨯ 653 mm ⨯ 242 mm Electronic Solar Switch Weight 35 kg Length ⨯ width ⨯ height of packaging 390 mm ⨯ 800 mm ⨯ 580 mm...
  • Page 89: Protective Devices

    SMA Solar Technology AG 12 Technical Data 12.3 Protective Devices DC reverse polarity protection Short-circuit diode DC disconnect device Electronic Solar Switch DC overvoltage protection Thermally monitored varistors AC short-circuit current capability Current control Grid monitoring SMA Grid Guard 2.1...
  • Page 90: Features

    12 Technical Data SMA Solar Technology AG 12.6 Features DC connection SUNCLIX DC connector AC connection Screw terminal Display LC text display Bluetooth Optional RS485, galvanically isolated Optional 12.7 Electronic Solar Switch Electrical endurance in the event of a short circuit,...
  • Page 91: Accessories

    13 Accessories You will find the corresponding accessories and spare parts for your product in the following STSatz_Zubehör overview. If required, these can be ordered from SMA Solar Technology AG or your specialist dealer. Designation Brief description SMA order number...
  • Page 92: Contact

    14 Contact SMA Solar Technology AG 14 Contact If you have technical problems concerning our products, contact the SMA Service Line. We require STSatz_Kontakt_Benötigte Daten the following information in order to provide you with the necessary assistance: • Inverter device type •...
  • Page 93 Legal Restrictions The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the purposes of evaluating the product or its correct implementation is allowed and does not require permission.

This manual is also suitable for:

10000tl11000tl

Table of Contents