General Data - SMA 5000TL Operating Manual

Sunny tripower
Hide thumbs Also See for 5000TL:
Table of Contents

Advertisement

11 Technical Data
Nominal AC current at 230 V
Nominal AC current at 240 V
Maximum output current
Total harmonic distortion of the output current with total harmonic
distortion of the AC voltage < 2%, and AC power > 50% of the
rated power
Maximum output current under fault conditions
Rated power frequency
AC power frequency*
Operating range at AC power frequency 50 Hz
Operating range at AC power frequency 60 Hz
Displacement power factor cos φ, adjustable
Feed-in phases
Phase connection
Overvoltage category in accordance with IEC 60664-1
* depending on the configured country data set
Efficiency
Maximum efficiency, η
European weighted efficiency, η

11.2 General Data

Width x height x depth, with Electronic So-
lar Switch
Weight of STP 5000TL-20 / 6000TL-20 /
7000TL-20 / 8000TL-20 / 9000TL-20 /
10000TL-20
Weight of STP 12000TL-20
Length x width x height of the packaging
Transport weight of STP 5000TL-20 /
6000TL-20 / 7000TL-20 / 8000TL-20 /
9000TL-20 / 10000TL-20
Transport weight of STP 12000TL-20
64
STP5-12TL-20-BE-en-15
max
EU
SMA Solar Technology AG
STP 12000TL-20
50 Hz / 60 Hz
45.5 Hz to 54.5 Hz
55.5 Hz to 64.5 Hz
0.8 underexcited to 1 to
0.8 overexcited
STP 12000TL-20
470 mm x 730 mm x 240 mm
37 kg
38 kg
798 mm x 598 mm x 398 mm
40 kg
41 kg
17.4 A
16.7 A
17.4 A
≤3 %
30 A
50 Hz
3
3
III
98.2 %
97.9 %
Operating Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8000tl10000tl9000tl12000tl6000tl7000tl