8 Configuration
• Select the parameter Minimum On power for MFR battery bank or
Mlt.BatCha.Pwr and set the desired value. This will configure the power threshold from
which the battery is to be charged.
• Select the parameter Minimum time before reconnection of MFR battery bank or
Mlt.BatCha.Tmm and set the desired value. This will configure the minimum time which
must elapse after charging the battery before the battery can be charged again.
8.9

Setting SMA OptiTrac Global Peak

For partially shaded PV modules, you should set the interval at which the inverter is to optimize the
MPP of the PV system. If you do not want to use SMA OptiTrac Global Peak feature, you can
deactivate the feature.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.5 "Changing Operating Parameters", page 49).
Procedure:
• Select the parameter Cycle time of the OptiTrac Global Peak algorithm or
MPPShdw.CycTms and set the required time interval. The ideal time interval is usually six
minutes. This value should only be increased if the shading situation changes extremely slowly.
☑ The inverter optimizes the MPP of the PV system at the predetermined time interval.
• In order to deactivate the SMA OptiTrac Global Peak feature, select the parameter OptiTrac
Global Peak switched on or set MPPShdw.IsOn to Off.