Vega VEGAPULS 62 Operating Instructions Manual page 46

4...20 ma/hart
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

Set up with the indicating and adjustment module PLICSCOM
Reset
46
Sensor-TAG
l
Displayed value
l
Display unit
l
Scaling
l
Current output
l
Unit of measurement
l
Language
l
The following safety-relevant data are not read out or written:
HART mode
l
PIN
l
SIL
l
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
Menu item
Max. adjustment
Min. adjustment
Medium
Vessel form
Damping
Linearisation
Sensor-TAG
Displayed value
Extended settings
Current output - characteristics
Current output - max. current
Current output - min. current
Current output - failure
Unit of measurement
The values of the following menu items are not reset to the
reset values (see chart) with "Reset":
Sensor-specific basic adjustment.
2)
Reset value
0 m(d)
30 m(d) (VEGAPULS 61, 63, 65, 67)
35 m(d) (VEGAPULS 62, 66)
70 m(d) (VEGAPULS 68)
Liquid
not known
0 s
linear
Sensor
Distance
None
4 ... 20 mA
20 mA
4 mA
<3.6 mA
m(d)
VEGAPULS 62 • 4 ... 20 mA/HART
2)