Set up with the indicating and adjustment module PLICSCOM
Carrying out min. ad-
justment
Carrying out max. ad-
justment
42
Start your parameter adjustment with the following menu items
of the basic adjustment:
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
Basic adjustment
Display
Diagnostics
Service
Info
2 Select the menu item "Basic adjustment" with [->] and
confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the suitable distance value in m for the empty vessel
(e.g. distance from the sensor to the vessel bottom)
corresponding to the percentage value.
5 Save the settings with [OK] and move to "Max. adjustment"
with [->].
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
2 Enter the appropriate distance value in m (corresponding
to the percentage value) for the full vessel. Keep in mind
that the max. level must lie below the dead band.
3 Save the settings with [OK] and move to "Medium
selection" with [->].