Mitsubishi GOT2000 Series User Manual page 313

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Error
Error message
code
698
Insufficient CoreOS version.
699
Insufficient BootOS version.
800
Abnormal module status
801
Abnormal baton passing status
802
Abnormal cyclic transmission status
803
Transient error
The cable on the IN side is
804
disconnected or is not connected.
The cable on the OUT side is
805
disconnected or is not connected.
840
PROFIBUS master is not started.
I/O setting of the PROFIBUS master
841
and slaves do not match.
850
CC-Link switch setting error
851
Abnormal cyclic transmission status
852
Abnormal host line status
853
Transient error
862
Critical link error
863
Incomplete configuration
864
Unrecoverable fault(s)
865
Recoverable fault(s)
*1
When an error occurs, "FF
Install the latest version of CoreOS.
Install the latest version of BootOS
Refer to explanations of SB0020 on the applicable network manual.
For the CC-Link IE Field Network, refer to the manual of MELSEC-Q CC-Link IE
Field Network master/local module.
Refer to explanations of SB0047 on the applicable network manual.
Refer to explanations of SB0049 on the applicable network manual.
Refer to explanations of SB00EE on the applicable network manual.
Refer to explanations of SB0067 on the applicable network manual.
Refer to explanations of SB0068 on the applicable network manual.
Turn on the PROFIBUS master module.
• Use the GSD file, a configuration file provided by MITSUBISHI. (Edit prohibited)
• Correct relevant settings, and turn off and then on the GOT.
• Check if the switch settings have no error.
• Check error codes stored in SW006A.
• Refer to explanations of SB006A on the applicable network manual.
Check if terminating resistors are connected.
Check error codes for the PLC CPU.
Check the parameter for the PLC CPU on the master station.
Check the error status of the master station.
Refer to explanations of SB006E on the applicable network manual.
Check if the cable is unplugged or not.
Refer to explanations of SB0090 on the applicable network manual.
Check the transient error occurrence status for each station stored in SW0094 to
SW0097.
Refer to explanations of SB0094.
The controller has failed, or has an error disabling network communication. (MAC IDs
are duplicated, or Bus-off is detected.) Check the controller.
The controller setting is not configured, or the setting is inadequate or incorrect.
Review the controller setting.
The controller has an uncorrectable error.
The error is automatically corrected.
If the module status LED indicator does not turn green, the controller may have a
failure.
" is stored to the channel No.
H
8.2 Error Codes and System Alarm List
Action
Channel
No. storage
8
8 - 13