Examples On How To Connect A Three Phase-To-Earth Connected Vt To The Ied - ABB REQ650 Applications Manual

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.4.3
72
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
100 V
110 V
115 V
120 V
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
Examples on how to connect a three phase-to-earth connected VT to
the IED
Figure
30
gives an example on how to connect a three phase-to-earth connected VT to
the IED. It as well gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
1MRK 505 291-UEN A
Application manual

Advertisement

Table of Contents
loading

Table of Contents