Section 10
Control
10.4
10.4.1
10.4.2
228
AutoCont and tAutoContWait , Automatic continuation to the next shot if
the CB is not closed within the set time
The normal setting is AutoCont = Off. The tAutoContWait is the length of time
STBRREC waits to see if the breaker is closed when AutoCont is set to On. Normally
the setting can be tAutoContWait=2 s.

Apparatus control

Identification

Function description
Bay control
Local remote
Local remote control

Application

The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck,
operator place selection and external or internal blockings.
The complete apparatus control function is not included in this
product, and the information below is included for understanding of
the principle for the use of QCBAY, LOCREM, and LOCREMCTRL
for the selection of the operator place.
Figure
94
gives an overview from what places the apparatus control function receive
commands. Commands to an apparatus can be initiated from the Control Centre (CC),
the station HMI or the local HMI on the IED front.
IEC 61850
IEC 60617
identification
identification
QCBAY
-
LOCREM
-
LOCREMCTRL
-
1MRK 505 291-UEN A
ANSI/IEEE C37.2
device number
-
-
-
Application manual