ABB REQ650 Applications Manual page 145

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

1MRK 505 291-UEN A
Application manual
t1: Time delay of the re-trip. The setting can be given within the range 0 – 60 s in steps
of 0.001 s. Typical setting is 0 – 50 ms.
t2: Time delay of the back-up trip. The choice of this setting is made as short as
possible at the same time as unwanted operation must be avoided. Typical setting is 90
– 200 ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
³
+
+
t
2
t
1
t
t
cbopen
BFP reset
_
EQUATION1430 V1 EN
where:
t
is the maximum opening time for the circuit breaker
cbopen
t
is the maximum time for breaker failure protection to detect correct breaker
BFP_reset
function (the current criteria reset)
t
is the safety margin
margin
It is often required that the total fault clearance time shall be less than a given critical
time. This time is often dependent of the ability to maintain transient stability in case
of a fault close to a power plant.
Protection
operate time
Normal t
Retrip delay t1
The fault
occurs
Trip and Start
CSPRBRF
IEC10000280 V1 EN
Figure 67:
Time Sequence
+
t
margin
cbopen
t
after re-trip
cbopen
t
BFPreset
Minimum back-up trip delay t2
Critical fault clearance time for stability
Section 6
Current protection
(Equation 44)
Margin
Time
IEC10000280-1-en.vsd
139