Insulation Gas Monitoring Function Ssimg; Identification; Application; Insulation Liquid Monitoring Function Ssiml - ABB REQ650 Applications Manual

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Section 12
Monitoring
12.10
12.10.1
12.10.2
12.11
12.11.1
12.11.2
12.12
12.12.1
278

Insulation gas monitoring function SSIMG

Identification

Function description
Insulation gas monitoring function

Application

Insulation gas monitoring function (SSIMG) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation gets blocked to minimize the risk of internal failure. Binary
information based on the gas pressure in the circuit breaker is used as input signals to
the function. In addition to that, the function generates alarms based on received
information.

Insulation liquid monitoring function SSIML

Identification
Function description
Insulation liquid monitoring function
Application
Insulation liquid monitoring function (SSIML) is used for monitoring the circuit
breaker condition. Proper arc extinction by the compressed oil in the circuit breaker is
very important. When the level becomes too low, compared to the required value, the
circuit breaker operation is blocked to minimize the risk of internal failures. Binary
information based on the oil level in the circuit breaker is used as input signals to the
function. In addition to that, the function generates alarms based on received
information.

Circuit breaker condition monitoring SSCBR

Identification
IEC 61850
IEC 60617
identification
identification
SSIMG
-
IEC 61850
IEC 60617
identification
identification
SSIML
-
1MRK 505 291-UEN A
ANSI/IEEE C37.2
device number
63
ANSI/IEEE C37.2
device number
71
Application manual

Advertisement

Table of Contents
loading

Table of Contents