ABB REQ650 Applications Manual page 73

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

1MRK 505 291-UEN A
L1
CT 600/5
Star Connected
Protected Object
IEC13000002 V4 EN
Figure 26:
Star connected three-phase CT set with star point towards the protected object
Application manual
L2
L3
IL1
IL2
IL3
IN
Where:
1)
The drawing shows how to connect three individual phase currents from a star connected
three-phase CT set to the three CT inputs of the IED.
2)
The current inputs are located in the TRM. It shall be noted that for all these current inputs the
following setting values shall be entered for the example shown in
CTprim=600A
CTsec=5A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.
In other words, currents are already measured towards the protected object.
Table continues on next page
IED
1
2
3
Section 4
Analog inputs
4
SMAI2
BLOCK
AI3P
REVROT
AI1
5
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
IEC13000002-4-en.vsdx
figure