Section 12
Monitoring
12.4.4
12.4.4.1
266
IEC05000652 V2 EN
Figure 104:
Calibration curves
Setting examples
Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
•
Measurement function (CVMMXN) application for a 110kV OHL
•
Measurement function (CVMMXN) application on the secondary side of a
transformer
•
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values
will be provided.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
Measurement function application for a 110kV OHL
Single line diagram for this application is given in figure 105:
1MRK 505 291-UEN A
Application manual