ABB REQ650 Applications Manual page 271

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

1MRK 505 291-UEN A
Application manual
Limits are directly set in applicable measuring unit, V, A , and so on,
for all measureing functions, except CVMMXN where limits are set
in % of the base quantity.
XHiHiLim: High-high limit.
XHiLim: High limit.
XLowLim: Low limit.
XLowLowLim: Low-low limit.
XLimHyst: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The parameter
PhaseAngleRef defines the reference.
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VNMMXU and
VMMXU) to get class 0.5 presentations of currents, voltages and powers. This is
accomplished by amplitude and angle compensation at 5, 30 and 100% of rated
current and voltage. The compensation curve will have the characteristic for
amplitude and angle compensation of currents as shown in figure
first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
Section 12
Monitoring
104
(example). The