Section 6
Current protection
112
A1
I>
t=0
t=t
1
The fault
Protection
occurs
B1 trips
IEC10000279 V1 EN
Figure 55:
Sequence of events during fault
where:
•
t=0 is when the fault occurs.
•
t=t1 is when the trip signal from the overcurrent protection at IED B1 is sent to the
circuit breaker. The operation time of this protection is
•
t1, t=t2 is when the circuit breaker at IED B1 opens. The circuit breaker opening
time is t2 - t1.
•
t=t3 is when the overcurrent protection at IED A1 resets. The protection resetting
time is t3 - t2.
To ensure that the overcurrent protection at IED A1, is selective to the overcurrent
protection at IED B1, the minimum time difference must be larger than the time t
There are uncertainties in the values of protection operation time, breaker opening
time and protection resetting time. Therefore a safety margin has to be included. With
normal values the needed time difference can be calculated according to equation 19.
D ³
+
+
t
40
ms
100
ms
EQUATION1266 V1 EN
where it is considered that:
•
the operate time of overcurrent protection B1 is 40 ms
•
the breaker open time is 100 ms
•
the resetting time of protection A1 is 40 ms
•
the additional margin is 40 ms
B1
I>
t=t
t=t
2
Breaker at
Protection
B1 opens
A1 resets
+
=
40
ms
40
ms
220
ms
1MRK 505 291-UEN A
Feeder
Time axis
3
IEC10000279-1-en.vsd
Application manual
.
3
(Equation 24)