ABB REQ650 Applications Manual page 28

Breaker protection
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Section 2
Application
22
132 kV Bus
132kV/110V
QB1
QC1
QA1
QC2
1000/1
QB9
QC9
132kV/110V
Other configured functions
Cond
Cond
TCS SCBR
SPVN ZBAT
DRP RDRE
IEC10000321 V3 EN
Figure 2:
Typical application example of the REQ650 A01 used as backup
protection in a single busbar single breaker arrangement when three-
phase trip is required
WA1
50BF
50
3I>>
CC RBRF
PH PIOC
IN>
51/67
3I>
51N/67N
EF4 PTOC
OC4 PTOC
59
3U>
OV2 PTOV
Function Enabled
in Settings
ANSI
Mont.
63
IEC61850
S SIMG
1MRK 505 291-UEN A
REQ650-A01 – Single Busbar Single breaker 10AI (4I+1I+5U)
Three phase variant
Meter.
V MMXU
79
0->1
94
1->0
SMB RREC
SMP PTRC
>
46
Iub
26
Cond
S SCBR
BRC PTOC
LC PTTR
52PD
Meter.
Meter.
CC RPLD
C MMXU
C MSQI
67N
IN<->
60FL
Meter.
SDE PSDE
SDD RFUF
CV MMXN
Wh<->
ETP MMTR
Meter.
Meter.
V MMXU
V MSQI
Function Disabled
in Settings
IEC
ANSI
IEC
IEC61850
Application manual
25
SYNC
SES RSYN
IEC10000321-3-en.vsd