CHAPTER 10: MAINTENANCE
panel, then check that the graphical front panel is plugged into the upper connection, not the lower silver connection
on the CPU module.
To upgrade software and firmware.
1.
Upgrade the EnerVista software as outlined in this chapter.
2.
Input the IP address and subnet mask of the relay on the front panel under Settings > Product Setup >
Communications > Network, and input the gateway address under Default IPv4 Route.
3.
Upgrade the firmware in the EnerVista software as outlined in this chapter, for example under Maintenance > Update
Firmware.
If you see error messages after the upgrade, disconnect power to the relay and shut down the software, then start
both again. If you see a flashing message about front panel communications trouble, check the connection of the
graphical front panel to the CPU module.
4.
In the EnerVista software, click the Device Setup button and refresh the order code for the device.
5.
Set the relay to Programmed mode under Settings > Product Setup > Installation.
6.
Update the EnerVista software to recognize the graphical front panel under Maintenance > Change Front Panel. This
setting does not display for units already with a graphical front panel.

10.11 Replace module

This section outlines how to replace a module.
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
To replace a module:
1.
Open the enhanced front panel to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the T35.
Figure 10-26: Modules inside relay with front cover open (enhanced front panel)
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
REPLACE MODULE
10
10-23