PRODUCT SETUP
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.
5.3.11.6 Event cause LED 1(9)
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  EVENT CAUSE LED 1(9)
 EVENT CAUSE LED 1
For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
— If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED 1 TYPE
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel RESET button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-16: Default input and output operand for event cause LEDs
LED
Event Cause LED 1
Event Cause LED 2
5
Event Cause LED 3
Event Cause LED 4
Event Cause LED 5
Event Cause LED 6
Event Cause LED 7
Event Cause LED 8
Event Cause LED 9

5.3.12 User-programmable self-tests

SETTINGS  PRODUCT SETUP  USER-PROGRAMMALBE SELF TESTS
 USER-PROGRAMMABLE
 SELF TESTS
5-122
LED 1 OPERAND:
LED PICKUP
LED 1 COLOR:
Green
LED 1 TYPE:
Self-Reset
Default input operand
Output operand
LED PICKUP
EVENT CAUSE LED 1
LED VOLTAGE
EVENT CAUSE LED 2
LED CURRENT
EVENT CAUSE LED 3
LED FREQUENCY
EVENT CAUSE LED 4
LED OTHER
EVENT CAUSE LED 5
LED PHASE A
EVENT CAUSE LED 6
LED PHASE B
EVENT CAUSE LED 7
LED PHASE C
EVENT CAUSE LED 8
LED NEUTRAL/GROUND
EVENT CAUSE LED 9
DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
RxGOOSE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
SFP MODULE FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
Range: FlexLogic operand
Range: Red, Green, Orange
Range: Self-Reset, Latched
Default color
Green
Orange
Orange
Orange
Orange
Orange
Orange
Orange
Orange
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS