PRODUCT DESCRIPTION
and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any standard web browser
(T35 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the
Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The T35 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
2
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device
Function
number
49
Thermal Overload Protection
50/87
Instantaneous Differential Overcurrent
50G
Ground Instantaneous Overcurrent
50P
Phase Instantaneous Overcurrent
51G
Ground Time Overcurrent
51P
Phase Time Overcurrent
81U
Underfrequency
87RGF
Restricted Ground Fault
87T
Transformer Differential
2-2
Figure 2-1: Single-line diagram
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION