GE T35 Instruction Manual page 369

Transformer protection system
Hide thumbs Also See for T35:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
SYSTEM SETUP
IEC 61850 functionality is permitted when the T35 is in "Programmed" mode and not in local control mode.
The switch element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagrams. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking open/close commands are provided. Note that
the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain close/open
command for a certain time, do so using the seal-in timers
and
, on the
SWITCH 1 OPEN SEAL-IN
SWITCH 1 CLOSE SEAL-IN
contact outputs using the "Seal-in" setting, or in FlexLogic.
Figure 5-75: Disconnect switch control logic (sheet 1 of 3)
5
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
5-167