Signal Sources - GE T35 Instruction Manual

Transformer protection system
Hide thumbs Also See for T35:
Table of Contents

Advertisement

SYSTEM SETUP
The
FREQUENCY AND PHASE REFERENCE
phase angle reference. The AC signal used is prioritized based on the AC inputs configured for the signal source. Phase
voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing (V
signals is used for frequency metering and tracking (V
open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal always displays zero degrees and all other phase angles are relative to this signal. If the
pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of phase angle indications between different UR-
series relays.
FREQUENCY TRACKING
frequency applications.
The frequency tracking feature functions only when the T35 is in the "Programmed" mode. If the T35 is "Not
Programmed," then metering values are available but can exhibit significant errors.
Systems with an ACB phase sequence require special consideration. See the Phase Relationships of Three-phase
Transformers section of chapter 5.
5

5.5.3 Signal sources

SETTINGS  SYSTEM SETUP  SIGNAL SOURCES  SOURCE 1(6)
 SOURCE 1
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter
represents either the first bank of four channels (1, 2, 3, 4) called "1" or the second bank of four channels (5, 6, 7, 8) called
"5" in a particular CT/VT module. See the Introduction to AC Sources section at the beginning of this chapter for details.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others are referred.
For example, the selection "F1+F5" indicates the sum of each phase from channels "F1" and "F5," scaled to whichever CT
has the higher ratio. Selecting "None" hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio
and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs are summed together.
5-144
setting determines which signal source is used (and hence which AC signal) for
is set to "Disabled" only in unusual circumstances; consult GE Grid Solutions for special variable-
SOURCE 1 NAME:
SRC 1
SOURCE 1 PHASE CT:
None
SOURCE 1 GROUND CT:
None
SOURCE 1 PHASE VT:
None
SOURCE 1 AUX VT:
None
= V
), while Clarke transformation of the phase
ANGLE REF
A
= (2V
- V
- V
) / 3) for better performance during fault,
FREQUENCY
A
B
C
Range: up to 20 alphanumeric characters
Range: None, F1,... up to any 6 CTs. Only Phase CT
inputs are displayed.
Range: None, F1,... up to any 6 CTs. Only Ground CT
inputs are displayed.
Range: None, F5, M5, U5
Only phase voltage inputs are displayed
Range: None, F5, M5, U5
Only auxiliary voltage inputs are displayed
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS