GE T35 Instruction Manual page 420

Transformer protection system
Hide thumbs Also See for T35:
Table of Contents

Advertisement

GROUPED ELEMENTS
GROUND TOC1 CURVE
GROUND TOC1 TD MULTIPLIER
Programming this value to zero results in an instantaneous response to all current levels above pickup.
GROUND TOC1 RESET
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The "Timed" reset
method can be used where the relay must coordinate with electromechanical relays.
GROUND TOC1 BLOCK
element.
GROUND TOC1 EVENTS
of events recorder.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
This channel can be also equipped with a sensitive input. The conversion range of a sensitive channel is from 0.002
to 4.6 times the CT rating.
5
5.7.5.3 Ground instantaneous overcurrent (ANSI 50G, IEC PIOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND IOC1(12)
 GROUND IOC1
5-218
— This setting selects the inverse time overcurrent curve style.
— This setting specifies a multiple of the base curve shape specified by the
— The "Instantaneous" reset method is intended for applications with other relays, such as most static
— Assertion of the operand assigned to this setting blocks operation of the ground time overcurrent
— This setting enables and disables the logging of ground time overcurrent events in the sequence
Figure 5-111: Ground TOC1 logic
GROUND IOC1
FUNCTION: Disabled
GROUND IOC1 SIGNAL
SOURCE: SRC 1
GROUND IOC1
PICKUP: 1.000 pu
GROUND IOC1 PICKUP
DELAY: 0.00 s
GROUND IOC1 RESET
DELAY: 0.00 s
GROUND IOC1 BLOCK:
Off
GROUND IOC1
TARGET: Self-reset
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
setting.
CURVE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents