GE T35 Instruction Manual page 526

Transformer protection system
Hide thumbs Also See for T35:
Table of Contents

Advertisement

DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES
Figure 8-5: Current distribution of D/D transformer with an a to b fault on the LV side
Test
Phase
Balanced
A
Condition
B
C
Min Pickup
A
B
C
Min Pickup
A
B
C
Slope 1
A
B
C
Slope 1
A
B
C
Intermediate
A
Slope 1 & 2
B
8
C
Intermediate
A
Slope 1 & 2
B
C
Slope 2
A
B
C
Slope 2
A
B
C
8-12
Injected current
W1 current
W2 current
0 ∠0°
0 ∠0°
0.435 ∠–90°
0.8 ∠–270°
0.435 ∠–270°
0.8 ∠–90°
0 ∠0°
0 ∠0°
0.09 ∠–90°
0.23 ∠–270°
0.09 ∠–270°
0.23 ∠–90°
0 ∠0°
0 ∠0°
0.21 ∠–90°
0.486 ∠–270°
0.21 ∠–270°
0.486 ∠–90°
0 ∠0°
0 ∠0°
0.651 ∠–90°
1.39 ∠–270°
0.651 ∠–270°
1.39 ∠–90°
0 ∠0°
0 ∠0°
0.63 ∠–90°
1.39 ∠–270°
0.63 ∠–270°
1.39 ∠–90°
0 ∠0°
0 ∠0°
1.2 ∠–90°
4.63 ∠–270°
1.2 ∠–270°
4.63 ∠–90°
0 ∠0°
0 ∠0°
0.8 ∠–90°
4.63 ∠–270°
0.8 ∠–270°
4.63 ∠–90°
0 ∠0°
0 ∠0°
0.315 ∠–90°
8.33 ∠–270°
0.315 ∠–270°
8.33 ∠–90°
0 ∠0°
0 ∠0°
0.18 ∠–90°
8.33 ∠–270°
0.18 ∠–270°
8.33 ∠–90°
Displayed current
Differential
Restraint
0 ∠0°
0 ∠0°
0 ∠0°
0.8 ∠–270°
0 ∠0°
0.8 ∠–90°
0 ∠0°
0 ∠0°
0.065 ∠0°
0.230 ∠–270°
0.065 ∠0°
0.230 ∠–90°
0 ∠0°
0 ∠0°
0.102 ∠0°
0.486 ∠–270°
0.101 ∠0°
0.486 ∠–90°
0 ∠0°
0 ∠0°
0.195 ∠0°
1.39 ∠–270°
0.195 ∠0°
1.39 ∠–90°
0 ∠0°
0 ∠0°
0.233 ∠0°
1.39 ∠–270°
0.233 ∠0°
1.39 ∠–90°
0 ∠0°
0 ∠0°
2.44 ∠–270°
4.63 ∠–270°
2.44 ∠–90°
4.63 ∠–90°
0 ∠0°
0 ∠0°
3.18 ∠–270°
4.63 ∠–270°
3.18 ∠–90°
4.63 ∠–90°
0 ∠0°
0 ∠0°
7.77 ∠–270°
8.33 ∠–270°
7.77 ∠–90°
8.33 ∠–90°
0 ∠0°
0 ∠0°
8 ∠–270°
8.33 ∠–270°
8 ∠–90°
8.33 ∠–90°
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: COMMISSIONING
Status
Not Applicable
Block
I
= 0.065 < Min PKP
d
Operate
I
= 0.101 > Min PKP
d
Block
I
I
/
= 14% < 15%
d
r
Operate
I
I
/
= 16.8% > 15%
d
r
Block
I
I
/
= 52.6%
d
r
< 60%
computed
Operate
I
/
I
= 68.8%
d
r
> 60%
computed
Block
I
/
I
= 93.2%
d
r
< Slope 2 = 95%
Operate
I
I
/
= 96%
d
r
> Slope 2 = 95%