5.0 Verify configuration

Use the following block examples to do basic configuration to the transmitter. For
more advanced configurations see the Rosemount 3051S F
Reference
Manual.
Note
DeltaV
users should use DeltaV Explorer for the resource and transducer blocks and
Control Studio for the function blocks.
5.1 To configure the AI block
AI block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
Parameters
Channel
L_Type
XD_Scale
Out_Scale
Note
Only select the units that are supported by the device.
Pressure example
Parameters
Channel
L_Type
XD_Scale
Out_Scale
Note
Only select the units that are supported by the device.
10
Enter data
1 = Pressure or 2 = Sensor temp or 3 = Mass flow
Direct, indirect, or square root
Scale and engineering units
Pa
bar
kPa
mbar
MPa
atm
Scale and engineering units
Enter data
1
Direct
See list of supported engineering units.
Set values outside operating range.
inH
O @ 68 °F
psi
2
mmH
O @ 68 °F
g/cm
2
ftH
O @ 68 °F
kg/cm
2
torr
June 2016
fieldbus
OUNDATION
inHg @ 0 °C
2
mmHg @ 0 °C
2
mmH
O @ 4 °C
2
inH
O @ 4 °C
2