FAAC 624 BLD Manual page 8

Control board
Hide thumbs Also See for 624 BLD:
Table of Contents

Advertisement

if you press F again (and hold it down), the display shows
the name of the next function, etc.
• when you reach the last function, press the push-button
F to exit programming, and the display resumes showing
the inputs status.
1ST LEVEL PROGRAMMING
Display
Function
LOADING PARAMETERS:
dF
00
Neutral condition
0 1
Default FAAC 1 loaded
02
Default RESERVED FOR FAAC
03
Default FAAC CITY loaded
04
Default FAAC CITY K loaded
00
LEAVE AT
IF YOU DO NOT WISH TO MAKE ANY
CHANGE TO THE PROGRAMMING.
For an explanation of the dF parameter
refer to page 8 chapter 5.2.
BUS ACCESSORY MENU
bu
For an explanation of this parameter refer to
page 8 chapter 5.3.
FUNCTION LOGICS:
LO
A
Automatic
A 1
Automatic 1
E
Semiautomatic
P
Parking
PA
Parking automatic
Cn
Condo
CA
Condo automatic
rb
Faac-City ( traffic bollard logic
C
Dead-man
r
Remote
Cu
Custom
PAUSE TIME:
PA
This operates only if an automatic
logic was selected. Can be adjusted
0
59
from
to
sec. in 1 second steps.
Subsequently, the display changes to
show minutes and tenths of a second
(separated by a dot) and time is adjusted
in 10 second steps, up to the maximum
4 . 1
value of
minutes.
e.g. if the display shows
time will be 2 min and 50 sec
POWER:
FO
Adjusts motor power.
0 1
= minimum power
50
= maximum power
LOOP 1:
L 1
If this function is enabled, the loop
connected to the Loop1 input will have
the OPEN function.
Y
= loop1 active
n o
= loop1 not active
Attention: if the function is not enabled,
loop1 status will nevertheless be available
on one of the outputs, if appropriately set
(see second level programming).
Default
00
E
)
20
2.5
the pause
,
.
50
no
7
Display Function
LOOP 2:
L 2
If this function is enabled, the loop
connected to Loop2 input will have the
SAFETY/CLOSE function, i.e. it will operate
as SAFETY during the closing stage, and
will command CLOSE to the board at
release.
Y
= loop2 active
n o
= loop2 not active
Attention: if the function is not enabled,
loop2 status will nevertheless be available
on one of the outputs, if appropriately
set.
SENSITIVITY LOOP 1
S 1
Regulates the sensitivity of the loop:
0 1
= minimum
1 0
= maximum
SENSITIVITY LOOP 2
S2
Regulates the sensitivity of the loop:
0 1
= minimum
1 0
= maximum
AUTOMATED SYSTEM STATUS:
St
Exit programming,
memory storage of data set and return to
automated system status view.
00
Closed
0 1
Opening pre-flashing
02
Opening
03
Open
04
In pause
05
Closing pre-flashing
06
Closing
07
Stopped ready to close
08
Stopped ready to open
09
Emergency opening
10
Closing safety device in operation
The display of the automated system
St
status
is of fundamental importance
for the operator assigned to installation/
maintenance, to distinguish the logical
processes the board performs during
movements.
If, for example, the automated system is
in CLOSED state
display. On reaching the command OPEN,
the display will change to
is enabled, or directly to
movement), to then display
the OPEN position.
Default
no
05
05
00
must be shown on the
0 1
, if pre-flashing
02
(the OPENING
03
on reaching