RS485: PIN OUT

Use RS485 to create a multi-drop network containing up to 32 devices.
Note: port #1is set to RS485
Note that the ports are not isolated. If
controller is used with a non-isolated
external device, avoid potential voltage
that exceeds +/- 10V. To avoid damaging
the system, all non-isolating device ports
should relate to the same ground signal.
Use shielded, twisted pair cables.
Minimize the stub (drop) length leading
from each device to the bus.
Ideally, the main cable should be run in and out of the network device.
Do not cross positive (A) and negative (B) signals. Positive terminals must be wired to positive and negative terminals to
negative.