Compressor Alarm; Warning; Black-Out - Emerson DIXELL iCHILL IC100D EVO Quick Reference Manual

Table of Contents

Advertisement

C
15.3
OMPRESSOR
Alarm
Alarm description
Code
Compressor (n) disabled (by dedicated procedure
C(n)dS
in menu function)
C(n)dt
Compressor (n) high discharge temperature
C(n)HP Compressor(n) high pressure switch
Compressor(n) oil pressure switch / Oil level
C(n)oP
switch
C1Pd
Compressor oil differential
C(n)tr
Compressor(n) overload
15.1

WARNING

Alarm
Code
AEP1
Evaporator 1 water pump maintenance
AEP2
Evaporator 2 water pump maintenance
ACP1
Condenser 1 water pump maintenance
ACP2
Condenser 2 water pump maintenance
AEun
Unloading by high evaporator inlet temperature
ASAn
Domestic hot water pump maintenance
ASUn
Solar panel water pump maintenance
ArtC
Clock to be set (the device if not powered for some days loses the time and the date)
ArtF
Clock failure
C(n)Mn Compressor (n) maintenance
b1Cu
Unloading by high or low evaporator or condenser temperature or pressure
b1Cu
Unloading by low evaporator temperature or pressure
b1rC
Recovery function disabled
b1Eu
Unloading by low evaporator outlet temperature
noL
Link problem between the Ichill and the remote keyboard
16

BLACK-OUT

After the black-out, when the power supply is restored:
1.
the instrument restores the same operating mode lost after the supply failure.
2.
if active at the power off, the defrost is aborted
3.
All the timers are reloaded
4.
The alarm, if actives in manual mode at the power down, is not reset
1592022020 Quick reference guide iCHILL 100DEVO rel. 1.0
A
LARM
Alarm description
Compressor
(n)
OFF
OFF
OFF
OFF
OFF
OFF
if is enabled by parameter the
switching OFF of all compressors
Compressors not involved
OFF
21/40