Output Channels #1, 2, 3 And 4 - Emerson OPM4001 Installation And Operation Manual

Opacity/dust density enhanced controller
Table of Contents

Advertisement

I N S T R U C T I O N
M A N U A L

OUTPUT CHANNELS #1, 2, 3 AND 4

OPM4001 ENHANCED Analog output
wiring list wiring list
Common for mA outputs - ACM
Positive 4-20mA output CH1 - Aout0
Positive 4-20mA output CH2 - Aout1
Positive 4-20mA output CH3 - Aout2
Positive 4-20mA output CH4 - Aout3
4-20MA
The OPM4001 ENHANCED comes with four, 4-20mA output channels. The ranges are set during factory testing to the information
supplied by the customers. Field changes can be made in the set up page. Maximum output Loop compliance is 500 Ohms.
Channel 1 Is dedicated to the Service Module display with F.S. -5 to 99.9% opacity.
Channel 2, 3 and 4 can be used for DAS, recorder etc. To utilize the current loops (max 500 ohms total). F.S. ranges are customer
selected.
R E V
4 . 2
36