Output Terminal Panel Familiarization - MULTIQUIP MQP56 Operation Manual

60hz generator (isuzu 4jj1x diesel engine)
Table of Contents

Advertisement

OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 6) shown below is
located on the right-hand side (left from control panel) of
the generator. Lift up on the cover to gain access to
receptacles and terminal lugs.
NOTICE
Terminal legs "O" and "Ground" are considered bonded
grounds.
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
120 VAC, 20 AMP
GFCI RECEPTACLES
RECEPTACLE
AND
CIRCUIT BREAKER
PANEL
PAGE 22 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)

OUTPUT TERMINAL PANEL FAMILIARIZATION

1Ø AND 3Ø,
NEUTRAL
480 -120 VAC
TERMINAL
OUTPUT TERMINALS
V
U
W
O
BLACK
RED
BLUE WHITE
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES
AUX. POWER RECEPTACLES
240/120V, 50 AMPS
Figure 6. Output Terminal Panel
OUTPUT TERMINAL FAMILIARIZATION
The "Output Terminal Panel " (Figure 6) is provided with
the following:
„ Three 240/120V output receptacles @ 50 amp
„ Three Circuit Breakers @ 50 amps
„ Two 120V GFCI receptacles @ 20 amp
„ Two Duplex Circuit Breakers @ 20 amps
„ Five Output Terminal Lugs ( U, V, W, O, Ground)
GROUND
TERMINAL
HARD WIRE
HOOKUP PANEL
GREEN
Y
W
X
CS-6369
TWIST-LOCK
ACCESS DOOR
LIFT TO OPEN

Advertisement

Table of Contents
loading

Table of Contents