GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel's Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Table 7. Voltages Available
Three Phase
208V
220V
(Switchable)
Single Phase
120V
127V
(Switchable)
PAGE 26 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
240V
416V
440V
480V
139V
240V
254V
277V

GENERATOR OUTPUTS

Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 8. Generator Maximum Amps
Rated Voltage
1Ø 120 Volt
1Ø 240 Volt
3Ø 240 Volt
3Ø 480 Volt
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available
at the GFCI receptacles when the output terminals and
twist lock receptacles are in use. Be careful that your load
does not to exceed the available current capability at the
receptacles.
Table 9. 1Ø GFCI Receptacle Load Capacity
KW in Use
Twist Lock (CS6369)
1Ø 240/120V
40.4
39.2
38.0
38.6
35.6
Table 10. 3Ø Generator Maximum Amps
KVA in Use
(UVWO Terminals)
3Ø 240/480V
70
65.8
61.7
57.5
53.4
Maximum Amps
155.5 X 2 amps (4 wire)
77.8 amps (4 wire)
168 amps
84 amps
Available Load
Current (Amps)
GFCI Duplex
5-20R 120V
0
5 amps/receptacle
10 amps/receptacle
15 amps/receptacle
20 amps/receptacle
Available Load
Current (Amps)
GFCI Duplex
5-20R 120V
0 amps/receptacle
5 amps/receptacle
10 amps/receptacle
15 amps/receptacle
20 amps/receptacle