OPERATION MANUAL MODEL MQP56 60HZ GENERATOR (ISUZU 4JJ1X DIESEL ENGINE) Revision #0 (06/14/17) To find the latest revision of this publication, visit our website at: www.mqpower.com THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.
1-888-327-4236 (TTY: 1-800-424-9153), go to http://www.nhtsa.dot.gov; or write to: Administrator NHTSA 1200 New Jersey Avenue S.E. Washington, DC 20590 You can also obtain information about motor vehicle safety from http://www.safecar.gov. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 3...
COULD result in DEATH or SERIOUS INJURY. CAUTION Indicates a hazardous situation which, if not avoided, COULD result in MINOR or MODERATE INJURY. NOTICE Addresses practices not related to personal injury. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 5...
Page 6
ALWAYS store generator properly when it is not being used. Generator should be stored in a clean, dry location out of the reach of children and unauthorized personnel. PAGE 6 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 7
NEVER touch the hot exhaust manifold, local Health and Safety Administrator. muffl er or cylinder. Allow these parts to cool before servicing generator. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 7...
Page 8
NEVER insert any objects into the output receptacles during operation. This is extremely dangerous. The possibility exists of electrical shock, electrocution or death. PAGE 8 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 9
The battery contains combustible gases and liquids. If these gases and liquids come into contact with a fl ame or spark, an explosion could occur. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 9...
Recyclers and manufacturers alike promote the process of recycling metal. Using a metal recycling center promotes energy cost savings. PAGE 10 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
BE CONNECTED TO A GROUND ROD. I M U M I N 2 . 4 T . / REFERENCE NEC 250 Figure 2. Typical Generator Grounding Application PAGE 14 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
ALWAYS consult with a licensed They are to resist damage to the bottom of the generator electrician. and to maintain alignment. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 15...
7. Frequency Meter — Indicates the output frequency main circuit breaker in the closed position (ON). in hertz (Hz). Normally 60 Hz. PAGE 18 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
175A main circuit breaker is provided. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine. Figure 12. Over Current Relay Figure 11. Connecting Loads PAGE 24 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
1800 3600 150 ft. 100 ft. 65 ft. 2400 4800 125 ft. 75 ft. 50 ft. CAUTION: Equipment damage can result from low voltage MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 25...
W and U terminals as indicated on the AC Voltmeter Gauge (Figure 16) Figure 15. AC Voltmeter Figure 16. AC Voltmeter Change-Over Switch Gauge MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 27...
To achieve a 3Ø 208V output the voltage selector switch Figure 20. UVWO Terminal Lugs must be in the 3Ø-240/139 position and the voltage 3Ø-240/139V Connections regulator must be adjusted to 208V.. PAGE 28 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 29
NOTICE ALWAYS make sure that the connections to the UVWO terminals are secure and tight. The possibility of arcing exists, that could cause a fire. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 29...
Table 11. Recommended Motor Oil Figure 29. Internal Fuel Tank System NOTICE DO NOT add fuel while engine is running. Stop engine and let cool before adding fuel. PAGE 30 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 31
ONLY use #2 diesel fuel when refueling. DO NOT OVERFILL fuel system. Leave room for fuel expansion. Fuel expands when heated (Figure 33). Figure 33. Fuel Expansion MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 31...
Page 32
60/40 antifreeze/water mix ratio. This ratio mix NEVER place hands near the belts or fan will provide protection to about -58°F (-50°C). while the generator set is running. PAGE 32 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 33
Tighten all hose clamps and check hoses for leaks. If any hose (fuel or oil) lines are defective replace them immediately. Figure 35. Battery Connections MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 33...
After completion of the pre-heating cycle, the light will go OFF and the engine will start up automatically. CORRECT INCORRECT Figure 37. Engine Enclosure Doors Figure 41. Pre-Heat Lamp PAGE 34 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Under normal operating conditions the coolant temperature should be between 167°~203°F (75°~95°C) (Green Zone). Figure 45. Voltmeter Meter Figure 49. Coolant Temperature Gauge MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 35...
7. Inspect entire generator for any damage or loosening of components that may have occurred during operation. EMERGENCY SHUTDOWN PROCEDURE 1. Place the ECU Control Switch (Figure 55) in the OFF/ RESET position. PAGE 36 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
1500 hrs. is not necessary. The emissions-related warranty is valid up to 1500 hrs. Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H PAGE 38 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 39
(secondary) that 7. Clean the secondary element (paper air filter) as is used as a backup filter should the primary element referenced in step 6. becomes damaged. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 39...
Page 40
7. Torque drain plug to 1.4 lb-ft (2.0 N . m). 8. Remove the air from the fuel system. Reference Isuzu Figure 58. Draining Fuel Filter PAGE 40 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 41
7. Reconnect all fuel lines and electrical components. suspension if necessary. Fuel Hoses — inspect nylon and rubber hoses for signs of wear, deterioration and hardening. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 41...
Page 42
1. When checking or adding oil, place the machine so the engine is level. 2. Pull the engine oil dipstick from its holder. 3. Determine if engine oil is low. Oil level should be PAGE 42 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
Page 43
3. Coat the rubber seal (gasket) surface of oil filter (Figure 65) with clean 15W-40 engine oil. 4. Install new oil filter first by hand until it makes contacts MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 43...
Page 44
If generator is mounted on a trailer, jack trailer up and place on blocks so tires do not touch the ground or block and completely remove the tires. PAGE 44 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
RECEPTACLE 125V 20A BLACK OVER CURRENT RELAY BLUE WHITE SELECTOR SWITCH BROWN YELLOW RY1,2 RELAY UNIT GREEN LIGHT BLUE RECTIFIER GRAY LIGHT GREEN VIOLET ORANGE PINK PAGE 46 — MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17)
“ON” position, the engine will not be stopped even if the starter switch is turned to the “OFF” position. In such case, turn the diagnostic switch to the “OFF” position. MQP56 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/14/17) — PAGE 49...