14.1.2 Parameters related to Relay Output

REL.UNI
REL.FUN
CONTAC.
SETP.
SETP.LO
SETP.HI
ACT.DIR
HYST
14
9116 UniverSal converter
Relay Units (for IN.TYPE ≠ TEMP):
PERC = Relay setpoint in percent of input range.
DISP = Relay setpoints and hysteresis values relates to DISP.LO
and DISP.HI (display units)
Relay Function:
OFF (Note 3 ) = Relay is always OFF
POW (Note 3 ) = Relay is always ON if power is applied
ERR = Relay is activated when sensor error is present
WIND = Relay is activated when input signal is between SETP.
LO and SETP.HI values
SETP = Relay is activated when input signal reaches SETP
value
Relay contact function:
N.C. = Normaly Closed relay contact (for REL.FUN = SETP)
N.O. = Normally Open relay contact (for REL.FUN = SETP)
O.I.W = Relay contact Open Inside Window (for REL.FUN =
WIND)
C.I.W = Relay contact Closed Inside Window (for REL.FUN =
WIND)
Relay setpoint value in REL.UNI units for IN.TYPE ≠ TEMP or
in UNIT for IN.TYPE = TEMP. (for REL.FUN = SETP)
Relay setpoint low value in REL.UNI units for IN.TYPE ≠ TEMP
or in UNIT for IN.TYPE = TEMP. (for REL.FUN = WIND)
Relay setpoint high value in REL.UNI units for IN.TYPE ≠ TEMP
or in UNIT for IN.TYPE = TEMP. (for REL.FUN = WIND)
Relay action for increasing or decreasing input signal
(for REL.FUN = SETP):
DECR = Relay activates when input signal ≤ SETP.
INCR = Relay activates when input signal ≥ SETP.
Hysteresis value in REL.UNI units for IN.TYPE ≠ TEMP or in
UNIT for IN.TYPE = TEMP. (for REL.FUN = SETP or WIND)
Version No. V3R0