14 Safe parameterisation - user responsibility

14.1

Safety-related configuration parameters

14.1.1 parameters related only to Channel 1

Name
CH1.TYp
I.RaNGe
CONNeC
uNIT
SeNSOR
pt.TYpe
10
9113 TeMpeRaTuRe / ma CONVeRTeR
Function
Selected input type:
TeMp = Temperature
CuRR = Current
Selected fixed input range for current measurements (for CH1.
TYp = CuRR):
0_20 = 0...20 ma (no sensor error detection!)
4_20 = 4...20 ma
Selected sensor connection type for RTD measurements (for
SeNSOR = Ni or pt):
2W = 2-wire
3W = 3-wire
4W = 4-wire
If 2W or 3W is selected, the end user must ensure that the
applied sensor wiring does not introduce failures exceeding the
requirements for the safety application.
Selected temperature unit (for CH1.TYp = TeMp):
°C = degrees Celsius
°F = degrees Fahrenheit
Selected temperature sensor type (for CH1.TYp = TeMp):
TC = Thermocouple
Ni = Ni RTD sensor
pt = pt RTD sensor
pt sensor type (for SeNSOR = pt):
}
10 = pt10
20 = pt20 (No short circuit detection!)
50 = pt50
100 = pt100
200 = pt200
250 = pt250
300 = pt300
400 = pt400
500 = pt500
1000 = pt1000
Version No. V5R0