PR 9116 Safety Manual page 36

Universal converter
Hide thumbs Also See for 9116:
Table of Contents

Advertisement

LERBAKKEN 10, 8410 ROENDE DENMARK
Hazardous area
Zone 0,1,2, 20, 21, 22
4-20 mA
Loop-powered
transmitter
T
Module 9116B 1/2
Terminal 54-52
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 μH
Module 9116B1
Term. 54-52; 51-52
Uo
28 V
Io
93 mA
Po
650 mW
Module 9116B2
Term. 54-52; 51-52
Uo
21.4 V
Io
93 mA
Po
650 mW
Revision date:
2012-07-04
34
54
53
52
51
44
43
42
+
41
-
54
53
52
51
44
43
42
41
Group
Co
Lo
IIC
80 nF
IIB
640 nF
16 mH 218 μH/Ω
IIA
2.1 μF
32 mH 436 μH/Ω
Group
Co
Lo
IIC
0.16 μF
IIB
1.13 μF
16 mH 218 μH/Ω
IIA
4.15 μF
32 mH 436 μH/Ω
Version Revision
V6 R0
9116 - Product Version 9116-003
Non Hazardous area
or Zone 2
-20 ≤Ta ≤ +60ºC
4501
34
33
32
31
14
13
12
11
9116
Power Rail
4501
34
33
32
31
14
13
12
11
9116
Power Rail
Lo/Ro
4 mH
54 μH/Ω
Lo/Ro
4 mH
54 μH/Ω
Prepared by:
PB
9116QI01
Status relay, terminal (33,34)
Non hazardous area installation
Voltage max:
125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max:
32 VAC / 32 VDC
Power max:
16 VA / 32 W
Current max:
0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Non hazardous area installation
Voltage max:
250 VAC / 30 VDC
Power max:
500 VA / 60 W
Current max:
2 A AC / 2A DC
Zone 2 installation
Voltage max:
32 V AC / 30 VDC
Power max:
64 VA / 60 W
Current max:
2 A AC / 2 ADC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
253 V max. 400 Hz
m:
Page:
3/4

Advertisement

Table of Contents
loading

Table of Contents