Periodic Proof Test Procedure; Procedures To Repair Or Replace The Product; Maintenance; Documentation For Routing Diagram - PR 9116 Safety Manual

Universal converter
Hide thumbs Also See for 9116:
Table of Contents

Advertisement

10 Periodic proof test procedure

Step
action
1
Bypass the safety PLC or take other appropriate action to avoid a false trip
Connect a simulator identical to the input setup
2
Apply input value corresponding to 0/100% output range
3
Observe whether the outputs acts as expected
4
Restore the input terminals to full operation
5
Remove the bypass from the safety PLC or otherwise restore normal operation
6
This test will detect approximately 95% of possible "du" (dangerous undetected) failures in the
device. The proof test is equivalent to the functional test.

11 Procedures to repair or replace the product

Any failures that are detected and that compromise functional safety should be reported to the
sales department at PR electronics A/S.
Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only.

12 maintenance

No maintenance required.

13 Documentation for routing diagram

The routing diagram is shown in section 16.2.
13.1

In general

When configuring the 9116, you will be guided through all parameters and you can
choose the settings which fit the application. For each menu there is a scrolling help
text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
1 will increase the numerical value or choose the next parameter
2 will decrease the numerical value or choose the previous parameter
3 will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding 3 will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0)
without saving the changed values or parameters.
13.2

further explanations

13.2.1 Password protection

9116 Universal converter
Access to the configuration can be blocked by assigning a password.
The password is saved in the device in order to ensure a high degree of
protection against unauthorised modifications to the configuration. Default
password 2008 allows access to all configuration menus.
Password protection is mandatory in SIL applications.
Version No. V3R0
safety Manual
9

Advertisement

Table of Contents
loading

Table of Contents