Dip-Switch Programming; Output Setup - PR 3100 Series Manual

Isolators and converters
Hide thumbs Also See for 3100 Series:
Table of Contents

Advertisement

The devices 3104, 3105 and 3109 can be configured via DIP-switches. The DIP-
switches are located on the side of the device and can be adjusted with a small
screwdriver or other implement.
The tables below show the configuration based on DIP-switch settings.
NA = no function of DIP-switch.
3104
Input setup
1
0...20 mA
OFF OFF OFF OFF
4...20 mA
OFF OFF ON OFF
0...10 V
OFF ON OFF OFF
2...10 V
OFF ON
0...5 V
OFF ON OFF ON
1...5 V
OFF ON
0...20 mA Tx ON OFF OFF OFF
4...20 mA Tx ON OFF ON OFF
18

dIP-SWItCH ProgrammIng

2
3
4
ON OFF
ON
ON
3100V1 0 6 -I N
Adjustment of DIP-switches.
Default factory settings are:
Input = 0...20 mA
Output = 0...20 mA
All DIP-switches in the OFF position

output setup

5
0...20 mA
OFF OFF OFF NA
4...20 mA
OFF ON OFF NA
0...10 V
ON OFF OFF NA
2...10 V
ON
0...5 V
ON OFF ON
1...5 V
ON
6
7
8
NA
NA
NA
ON OFF NA
NA
NA
NA
ON
ON
NA
NA
CONTENTS
9
10
NA
NA
NA
NA
NA
NA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

31033104310531083109

Table of Contents